GPN1-12kV Ka taea te tango i te Whakawhitinga Whakawhitinga Whakakahuria AC Metal-clad
Ambient huru
Te pāmahana ambient: -25 ℃ ~ + 45 ℃, toharite ia rā: ≤35 ℃
Te teitei: 1000m( Paerewa);ka taea ki te 4500m mo te ota motuhake;
Haumākū pātahi: ia rā toharite ≤95%, marama toharite ≤90%;
Te kaha o te ru ≤8 tohu;
Ko nga waahi e tika ana kia noho kore i te mura o te ahi, te pahū, te waikura me te wiri nui.
Tauira
Hua āhuatanga
1) E tika ana tenei hua mo a maatau ake hanga GPVN-12kV/17Kv/24kV kua whakauruhia, karekau ranei, karekau maru, arai iahiko korehau a ABB, VD4 ranei.
2) To tatou production whirihoranga GPVC korehau contactor - huinga fuse ranei ABB kamupene o VC korehau contactors, e taea te tito o FC koropiko cubicle, ki te whakatau i te pūnaha hiko o tipu mana me te tono o te tahi atu hinonga ahumahi me te maina.
3) Ma te whakamahi i te pereti maitai konumohe-konutea pai na roto i nga taputapu miihini CNC kua huihuia ki roto i te rūnanga, me te whakamahi i te tukanga piko rua, ka tino pai ake te kaha o te rūnanga.
4) Mata tatau i te epoxy resin electrostatic paura rehu tukanga, ātete o te waikura, hāoratanga, pānga me te adhesion kaha.
5) Ko te rūnanga kua oti te whakakii i te hanganga kua oti te whakakakahu, kua tino wehea nga waahanga mahi.Ka tutakina te tatau, ka taea e ia te whakatutuki i te mahi o te kaitarai ara iahiko me te whakawhiti whenua.
6) Tikanga taraiwa hurihuri tika, whakarite i te trolley me te pai o te whakawhiti.
7) Mahere tuatahi tino pai ki te whakatutuki i nga momo hiahia o nga kaiwhakamahi, ka taea ai te mahere taraka rua.
8) Whakawhiti whenua tere mo te papa whenua me nga waahi poto, me te whakatutuki i te mahi hiko (Motorized).
9) Maamaa me te whai hua "Rima Haumaru" ka taea te aukati i te kino me te whakarite i te haumaru o te kaiwhakahaere.
10) No te momo Arc-proof a Switchgear, kei runga ake o te wahanga pahi, Ko te wahanga wehenga ara iahiko korehau, me te wahanga taura taura he taputapu awhina pehanga.
11) He nui te waahi o te waahanga taura, ka taea te hono atu ki te tini o nga taura, me te whakarite i te teitei whakaurunga o te mono taura.
12) Whakatauranga whakamarumaru tino (IP4X), kia pai ai te aukati i nga mea kee, i te whakaekenga kino ranei.
13) Ko te punaha tuarua e whai ake nei i te taputapu aroturuki haumaru he mahi tirotiro whaiaro me te whakawhitiwhiti korero raraunga, rorohiko whakauru mohio, ki te whakatutuki i te mana mamao, te waea waea mamao, te tirohanga mamao, te whakarereketanga mamao.
14) Tutaki GB3906, GB / T11022, DL404 me IEC60298, IEC62271-1 paerewa, a na roto i te momo whakamatautau matawhānui me te whakamatautau papaa (3000 m).
15) Kua paahitia nga whakamatautau hototahi hiko i roto i te taiwhanga whakamatautau taputapu ngaohiko teitei.
A.Whakaahuatanga Hangarau Mo te 12Kv switchgear
Tūemi | Waeine | Raraunga | |
Ngaohiko whakatau | kV | 6~12 | |
auau kua tohua | Hz | 50/60 | |
Kua whakatauhia o naianei | A | 630~4000 | |
Te taumata whakamarumaru kua whakatauhia | 1min auau hiko (Wahanga ki te whenua / puta noa i nga hoapaki tuwhera) | kV | 42/48 |
Ka mau te hihiko uira i te ngaohiko (Wāhanga ki te whenua/puta noa i nga hoapā tuwhera) | kV | 75/85 | |
Pae pahi matua e whakatau ana i naianei | A | 1250,1600,2000,2500,4000 | |
I whakatauhia te pae pahi iti i naianei | A | 630,1250,1600,2000,2500,3150 | |
I whakatauhia he wa poto ka tu ki naianei(4s) | kA | 16,20,25,31.5,40,50 | |
Ko te tihi kua whakatauhia ka mau i te naianei | kA | 40,50,63,80,100,125 | |
Tohu tiaki | Whakapiri IP4X, IP2X(kua tuwhera te tatau VCB) | ||
Te ahu whakahuahua(whanui/hohonu/teitei) | mm | 650(800,1000) /1500(1300,1670,2000) /2300 | |
Taumaha | kg | 500~1200 |
Te tuhi hanganga o te cubicle 630A~1250A
Te tuhi hanganga o te cubicle 1600A~4000A
B.Main tawhā hangarau tepu mo 17.5kV switchgear
Kao. | Ingoa | Waeine | Raraunga | |
1 | Ngaohiko whakatau | kV | 15/17.5 | |
2 | Te taumata whakamarumaru kua whakatauhia | 1 min te auau hiko whakaahuru ngaohiko (RMS) | kV | 50 |
Ko te kaha o te rama ka mau te ngaohiko (te tihi) | 95 | |||
3 | Kua whakatauhia o naianei | A | 630~4000 | |
4 | I whakatauhia te naianei whakatuwhera iahiko-poto | kA | 50 | |
5 | auau mana whakatau | Hz | 50/60 | |
6 | Whakatauhia te iahiko-poto hanga naianei(te tihi) | kA | 130 | |
7 | Ko te tihi kua whakatauhia ka mau i te naianei | kA | 130 | |
8 | I whakatauhia mo te wa poto ka tu i te naianei | kA | 50 | |
9 | Te ora hiko | wā | 20 | |
10 | I whakatauhia te roanga o naianei iahiko-poto | s | 4 | |
11 | Te ora miihini o VCB | wā | 10000 | |
12 | Te tohu whakamarumaru o te cubicle | Whakapiri IP4X, IP2X(kua tuwhera te tatau VCB) | ||
13 | Rahi Whakahuahua (W*D*H) | mm | 800/1000*1500/1670*2300 | |
14 | Taumaha | kg | 500~1200 |
C.Whakaahuatanga hangarau mo te 24kV switchgear
Tūemi | Waeine | Raraunga | |
Ngaohiko whakatau | kV | 24 | |
auau kua tohua | Hz | 50/60 | |
Kua whakatauhia o naianei | A | 630,1250, 1600, 2500, 3150, 4000 | |
Te taumata whakamarumaru kua whakatauhia | 1min auau hiko (waahanga ki te whenua / puta noa i nga hoapaki tuwhera) | kV |
65 |
Ka mau te hihiko uira i te ngaohiko (waahanga ki te whenua / puta noa i nga hoapaki tuwhera) | kV |
125 | |
I whakatauhia he wa poto ka tu ki naianei(4s) | kA | 20, 25, 31.5 | |
Ko te tihi kua whakatauhia ka mau i te naianei | kA | 50, 63, 80 | |
Tohu tiaki | Whakapiri: IP4X, tuwhera tatau: IP2X | ||
Te ahu whakahuahua(whanui x hohonu x teitei) | mm | 1000(800)x1820(1500)x2430(2300) | |
Taumaha | kg | 1200-1500 |
1. Ko te kaha taiawhio poto o CT me whakaaro motuhake;
2. Ko te hoahoa o te raina i runga i te tuara o waho me whai kohanga taapiri.