40.5kV SF6 Kaiwhati Iahiko Rangatū GPFN
Tauira me te Tikanga
Whakamahia nga Tikanga Taiao
a.Te teitei: kaua e neke ake i te 1000m
b.Te pāmahana ambient: -15℃~+40℃, ko te pāmahana toharite o ia ra kaore e neke ake i te +35℃
c.Te haumākū o te taiao: te haumākū whanaunga toharite o ia rā: ≤95% te haumākū whanaunga toharite o ia marama: ≤90%
Te pēhanga kohu toharite ia rā: ≤2.2x10-3 MPa Te pēhanga kohu toharite ā-marama: ≤1.8x10-3MPa
d.Te kaha o te ru: kaua e neke ake i te 8 nga nekehanga
e.Wāhi whakamahi: Ko te hau a tawhio noa e kore e tino pokea e te puehu, te auahi, te hauwaa me te karekau ranei, te kohu, te kohu tote ranei.
Tuhipoka: Ki te kore e tutukihia e te taiao whakamahi nga tikanga o runga ake nei, tena koa korero ki ta maatau kamupene.
Tawhā Hangarau
Kao. | Nga taonga | Waeine | Raraunga | |||
1 | Ngaohiko whakatau | kV | 40.5 | |||
2 | auau kua tohua | Hz | 50 | |||
3 | 1min te kaha o te kaha te tu i te ngaohiko | I waenganui i nga pou, Ki te whenua | kV | 95 | ||
Nga whati | 118 | |||||
Hiringa uira te pupuri ngaohiko | I waenganui i nga pou, Ki te whenua | 185 | ||||
Nga whati | 215 | |||||
4 | Kua whakatauhia o naianei | A | 1250 1600 2000 2500 | |||
5 | I whakatauhia mo te wa poto ka mau i naianei (RMS) | kA | 25 | 31.5 | ||
6 | Ko te tihi kua whakatauhia ka mau i te naianei | 63 | 80 | |||
7 | I whakatauhia te naianei pakaru iahiko poto (RMS) | 25 | 31.5 | |||
8 | Whakatauhia te iahiko-poto e hanga ana (te uara teitei) | 63 | 80 | |||
9 | Kua whakatauhia te roanga iahiko poto | s | 4 | |||
10 | Kua whakatauhia te raupapa o nga mahi | O-0.3s-CO-180s-CO | ||||
11 | I whakatauhia i waho-o-waahanga he he pakaru te naianei | kA | 21.7 | 27.4 | ||
12 | Whakatauhia te whakamatautau whakawhiti o naianei e utu ana i te taura | A | 50 | |||
13 | Whakatauria kotahi/hoki-ki-muri peeke peeke pakaru i naianei | 800/800 | ||||
14 | Te oranga miihini | wā | 10000 | |||
15 | Nga wa pakaru iahiko poto | wā | 30 | |||
16 | Te ara iahiko tuarua 1 min te kaha o te kaha ka mau te ngaohiko | 2000 | ||||
17 | Ngaohiko whakahaere kua whakatauhia | Kati te porowhita | V | DC110/220, AC220 | ||
Whakatuwhera i te porowhita | V | DC110/220, AC220 | ||||
18 | Ngaohiko whakatau o te nekeneke rokiroki pūngao | W | DC110/220, AC220 | |||
19 | Kua whakatauhia te mana o te motuka rokiroki hiko | s | 250 | |||
20 | Wā rokiroki pūngao (ngaohiko whakatau) | s | ≤10 | |||
21 | Te pehanga whakatau o te hau SF6 (te pehanga ine i te 20°C) | Mpa | 0.350+0.02 | |||
22 | Te pehanga whakaoho | Mpa | 0.29±0.01 | |||
23 | Te pehanga mahi iti (pehanga aukati) | Mpa | 0.28±0.01 | |||
24 | Reiti turuturu ia tau | % | ≤0.5 | |||
25 | Te makuku hau | μL/L | ≤150 | |||
26 | Te nuku whakapänga whiu | mm | ≥78 | |||
27 | Mokowā Whakapā | mm | 50±1.5 | |||
28 | Te wa whakatuwhera | ms | 60~78 | |||
29 | Te wa kati | ms | 65~95 | |||
30 | Ko te kati me te whakatuwhera i nga wahanga e toru ehara i te waa | ≤5 | ||||
31 | Toharite tere whakatuwheratanga (i roto i te 10ms i muri i te haurua) | ms | 2.2~2.8 | |||
32 | Te tere kati (i roto i te 10ms i muri i te haurua ara) | ms | ≥1.5 | |||
33 | Ātete koropiko matua conductive | μΩ | ≤32(Kaata Pupuri) | ≤20(Momo Pumau) |